Abstract

In this study, we examined the survey of indoor environment in a university lecture room is a place of intellectual production in young people, about the impact the indoor environment is given to the learning efficiency. The following findings were obtained from this measurement and questionnaire survey.
The lecture room air temperature was about 24 –28°C, relative humidity was 40 –80%. The concentration of carbon dioxide was less than 1000 ppm, the illuminance was about 650 –1300 lx, the noise level was 50~70 dB average. Satisfaction with the thermal environment and air environment was the result of a higher level of importance than the sound environment, light environment, the space environment. Indoor thermal environment was satisfactory indoor temperature is in the range of about 19 –26.5°C.